Nothing must be cut at the top at all and the certification label must remain intact.
Fire door threshold gap.
I work in a relatively new office buiding that has internal fire doors with cold smoke seals and the gaps under the doors range from 5mm to 10mm.
Bs9999 2008 recommends for fire doors with cold smoke control that the threshold gap should be either less than 3mm in height or should be fitted with a threshold seal.
The gap between door and frame at the top and sides should be 2 4 mm and the threshold gap as per manufacturers instructions typically around 8 10 mm the certificate will include details of this.
The gap between the door and the frame is extremely important and must be suitable for the intumescent seal fitted.
The artificial seal may be any material such as an impermeable sheet or tape by testing air infiltration with the artificial bottom seal in place any air that.
When speaking with manufacturers however a common statement is that a fire doors gap of up to 8 mm underneath the door is permissible.
Bs9999 2008 recommends for fire doors with cold smoke control that the threshold gap should be either less than 3mm in height or should be fitted with a threshold seal.
Approved document f ventilation in domestic buildings a ventilation gap totalling 7600 mm is recommended at the threshold of the door to allow.
If a door is to work effectively in its normal role the door leaf must be free to move within the frame and in order to achieve this there must be a gap around the perimeter.
Underneath the fire door a gap of 8mm is traditionally acceptable although for fire doors that are required to limit spread of cold smoke only 3 mm is permissible with a threshold seal to be fitted if the gap is bigger.
It is through extensive testing of fire rated doorsets together with knowledge of the pressure regime within a fire test that a larger gap is permitted at the threshold of the door.
How much can you cut off a fire door.
Mind the gap fire door seals fire doors play a crucial role in restricting the spread of fire and smoke.
The ul 1784 test standard states in order to obtain information on the extent of air leakage at the ungasketed bottom gap of a test sample an artificial seal may be applied to the bottom 6 inches 152 4 mm of the test sample.